Back to the backflow review queue

Backflow assembly test: 5622 Sycamore Rd

Approved

Filed Feb 22, 2025 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 22, 2025
Assembly type
RP
Serial number
K222662
Size
3/4
Test gauge serial
G-2268
Gauge calibration date
Jul 31, 2024
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-22-01356
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5622 Sycamore Rd
Owner: Alex Kessler
Parcel 059-22-01356