Backflow assembly test: Crossroads Grill

Approved

Filed Jan 8, 2026 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 8, 2026
Assembly type
RP
Serial number
B375921
Size
1 1/2
Test gauge serial
G-7766
Gauge calibration date
Sep 6, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 059-57-01066
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6529 Meadow Lark Dr
Owner: Ellery Holdings LLC
Parcel 059-57-01066