Back to the backflow review queue

Backflow assembly test: 1478 Hickory Way

Approved

Filed Mar 30, 2026 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 30, 2026
Assembly type
DC
Serial number
K601767
Size
3/4
Test gauge serial
G-5069
Gauge calibration date
Sep 2, 2025
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 059-39-01281
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1478 Hickory Way
Owner: Riley Calloway
Parcel 059-39-01281