Backflow assembly test: 8999 Laurel Dr
ApprovedFiled Jul 23, 2026 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 23, 2026
- Assembly type
- DC
- Serial number
- W729858
- Size
- 3/4
- Test gauge serial
- G-4722
- Gauge calibration date
- May 12, 2026
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ramirez, current on the service date
- All required fields present
- Address matches parcel 059-40-01019
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8999 Laurel Dr
Owner: Hayden Okafor
Parcel 059-40-01019