Back to the backflow review queue

Backflow assembly test: Crossroads Market

Approved

Filed Sep 27, 2025 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 27, 2025
Assembly type
RP
Serial number
Z219039
Size
1 1/2
Test gauge serial
G-9843
Gauge calibration date
Mar 4, 2025
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-85-01344
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2600 Orchard Rd
Owner: Marsh Holdings LLC
Parcel 059-85-01344