Backflow assembly test: 1198 Old Church Trl
ApprovedFiled Jul 24, 2025 by Hayden Pruitt, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 24, 2025
- Assembly type
- RP
- Serial number
- K902383
- Size
- 1
- Test gauge serial
- G-2785
- Gauge calibration date
- Mar 27, 2025
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Pruitt, current on the service date
- All required fields present
- Address matches parcel 055-23-01019
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1198 Old Church Trl
Owner: Riley Brandt
Parcel 055-23-01019