Back to the backflow review queue

Backflow assembly test: 3955 Meadow Lark Rd

Approved

Filed Feb 14, 2025 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 14, 2025
Assembly type
RP
Serial number
Z628027
Size
3/4
Test gauge serial
G-1833
Gauge calibration date
Oct 17, 2023
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
2.4 psid
Relief valve opened at
2.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Brandt, current on the service date
  • All required fields present
  • Address matches parcel 055-80-01281
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3955 Meadow Lark Rd
Owner: Hayden Hollins
Parcel 055-80-01281