Back to the backflow review queue

Backflow assembly test: 8205 Stone Gate Dr

Approved

Filed Mar 18, 2026 by Parker Brandt, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 18, 2026
Assembly type
RP
Serial number
Z880898
Size
1
Test gauge serial
G-8194
Gauge calibration date
Sep 12, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Brandt, current on the service date
  • All required fields present
  • Address matches parcel 055-11-01133
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8205 Stone Gate Dr
Owner: Alex Harlow
Parcel 055-11-01133