Back to the backflow review queue

Backflow assembly test: 7268 Laurel Trl

Approved

Filed May 17, 2025 by Cameron Ellery, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 17, 2025
Assembly type
DC
Serial number
W538133
Size
3/4
Test gauge serial
G-9170
Gauge calibration date
Feb 20, 2025
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Ellery, current on the service date
  • All required fields present
  • Address matches parcel 055-17-01232
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7268 Laurel Trl
Owner: Cameron Hollins
Parcel 055-17-01232