Back to the backflow review queue

Backflow assembly test: 798 Quarry Rd

Approved

Filed Apr 12, 2024 by Emerson Calloway, Ridge Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 12, 2024
Assembly type
RP
Serial number
A136386
Size
3/4
Test gauge serial
G-1528
Gauge calibration date
Nov 18, 2023
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-90-01199
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

798 Quarry Rd
Owner: Riley Marsh
Parcel 055-90-01199