Backflow assembly test: 9638 Mill Creek Way

Approved

Filed Dec 29, 2023 by Parker Brandt, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 29, 2023
Assembly type
RP
Serial number
Z700780
Size
3/4
Test gauge serial
G-2377
Gauge calibration date
Mar 9, 2023
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Brandt, current on the service date
  • All required fields present
  • Address matches parcel 055-11-01336
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9638 Mill Creek Way
Owner: Cameron Benton
Parcel 055-11-01336