ApprovedFiled Jun 3, 2025 by Hayden Fairley, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 3, 2025
- Assembly type
- RP
- Serial number
- B290360
- Size
- 3/4
- Test gauge serial
- G-1539
- Gauge calibration date
- Aug 21, 2024
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Fairley, current on the service date
- All required fields present
- Address matches parcel 055-89-01165
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.