Back to the backflow review queue

Backflow assembly test: 6284 Fox Run Ct

Approved

Filed Oct 20, 2025 by Emerson Calloway, Ridge Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 20, 2025
Assembly type
RP
Serial number
W207706
Size
1
Test gauge serial
G-6864
Gauge calibration date
Jan 20, 2025
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-69-01090
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6284 Fox Run Ct
Owner: Quinn Benton
Parcel 055-69-01090