Backflow assembly test: 7026 Fox Run Dr
ApprovedFiled Jul 22, 2025 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 22, 2025
- Assembly type
- RP
- Serial number
- B578438
- Size
- 3/4
- Test gauge serial
- G-6872
- Gauge calibration date
- Apr 26, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Brandt, current on the service date
- All required fields present
- Address matches parcel 055-23-01059
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7026 Fox Run Dr
Owner: Morgan Danner
Parcel 055-23-01059