Backflow assembly test: 7026 Fox Run Dr

Approved

Filed Jul 22, 2025 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 22, 2025
Assembly type
RP
Serial number
B578438
Size
3/4
Test gauge serial
G-6872
Gauge calibration date
Apr 26, 2025
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
1.6 psid
Relief valve opened at
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Brandt, current on the service date
  • All required fields present
  • Address matches parcel 055-23-01059
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.