Backflow assembly test: 7684 Ridgeview Ln
ApprovedFiled Nov 7, 2026 by Cameron Ellery, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 7, 2026
- Assembly type
- DC
- Serial number
- W633986
- Size
- 3/4
- Test gauge serial
- G-9374
- Gauge calibration date
- Apr 3, 2026
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Ellery, current on the service date
- All required fields present
- Address matches parcel 055-91-01251
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7684 Ridgeview Ln
Owner: Avery Wexler
Parcel 055-91-01251