Backflow assembly test: 1600 Hickory Trl

Approved

Filed Aug 25, 2023 by Hayden Pruitt, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 25, 2023
Assembly type
DC
Serial number
A537196
Size
1
Test gauge serial
G-2652
Gauge calibration date
Jan 19, 2023
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 055-45-01107
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1600 Hickory Trl
Owner: Jordan Brandt
Parcel 055-45-01107