Backflow assembly test: Corner Diner

Approved

Filed Nov 14, 2025 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 14, 2025
Assembly type
RP
Serial number
A392513
Size
2
Test gauge serial
G-5315
Gauge calibration date
Dec 18, 2024
Check valve 1
0.8 psid
Check valve 1 closed tight
No
Check valve 2
2.6 psid
Relief valve opened at
3.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-17-01326
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

890 Hickory Ln
Owner: Ellery Holdings LLC
Parcel 055-17-01326