Backflow assembly test: Crossroads Grill
ApprovedFiled Nov 1, 2025 by Cameron Ellery, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 1, 2025
- Assembly type
- RP
- Serial number
- Z998279
- Size
- 1 1/2
- Test gauge serial
- G-6873
- Gauge calibration date
- Mar 23, 2025
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Ellery, current on the service date
- All required fields present
- Address matches parcel 055-64-01131
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8830 Sycamore Ln
Owner: Danner Holdings LLC
Parcel 055-64-01131