Back to the backflow review queue

Backflow assembly test: 6813 Spring Branch Rd

Approved

Filed Dec 4, 2025 by Cameron Ellery, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 4, 2025
Assembly type
RP
Serial number
W207075
Size
1
Test gauge serial
G-5594
Gauge calibration date
Nov 3, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Ellery, current on the service date
  • All required fields present
  • Address matches parcel 055-62-01166
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6813 Spring Branch Rd
Owner: Casey Okafor
Parcel 055-62-01166