Back to the backflow review queue
Backflow assembly test: 5260 Old Church Trl
ApprovedFiled May 8, 2024 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 8, 2024
- Assembly type
- RP
- Serial number
- A333000
- Size
- 1
- Test gauge serial
- G-2218
- Gauge calibration date
- Apr 4, 2024
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Hollins, current on the service date
- All required fields present
- Address matches parcel 053-92-01093
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
5260 Old Church Trl
Owner: Logan Nguyen
Parcel 053-92-01093