Backflow assembly test: 8033 Hickory Ln
ApprovedFiled Dec 16, 2024 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 16, 2024
- Assembly type
- DC
- Serial number
- K524655
- Size
- 3/4
- Test gauge serial
- G-1545
- Gauge calibration date
- Oct 14, 2023
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Pruitt, current on the service date
- All required fields present
- Address matches parcel 053-76-01310
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.