Back to the backflow review queue

Backflow assembly test: Two Rivers Brewing Co

Approved

Filed Jul 29, 2025 by Parker Fairley, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 29, 2025
Assembly type
RP
Serial number
Z388589
Size
1 1/2
Test gauge serial
G-8014
Gauge calibration date
May 13, 2025
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 053-20-01054
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2293 Mill Creek Trl
Owner: Calloway Holdings LLC
Parcel 053-20-01054