Back to the backflow review queue
Backflow assembly test: 6821 Fox Run Trl
ApprovedFiled Nov 9, 2026 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 9, 2026
- Assembly type
- DC
- Serial number
- B442011
- Size
- 1
- Test gauge serial
- G-1475
- Gauge calibration date
- May 13, 2026
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Hollins, current on the service date
- All required fields present
- Address matches parcel 053-75-01085
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6821 Fox Run Trl
Owner: Cameron Ashby
Parcel 053-75-01085