Backflow assembly test: Riverside Pizza
ApprovedFiled Aug 15, 2025 by Rowan Benton, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 15, 2025
- Assembly type
- DC
- Serial number
- K767627
- Size
- 4
- Test gauge serial
- G-6802
- Gauge calibration date
- Apr 16, 2025
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Benton, current on the service date
- All required fields present
- Address matches parcel 053-50-01208
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4864 Sycamore Rd
Owner: Vance Holdings LLC
Parcel 053-50-01208