Back to the backflow review queue

Backflow assembly test: 4384 Spring Branch Trl

Approved

Filed Sep 11, 2025 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 11, 2025
Assembly type
RP
Serial number
A103391
Size
3/4
Test gauge serial
G-4537
Gauge calibration date
May 2, 2025
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 053-83-01062
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4384 Spring Branch Trl
Owner: Rowan Hollins
Parcel 053-83-01062