Back to the backflow review queue

Backflow assembly test: 670 Quarry Rd

Approved

Filed Jan 12, 2026 by Parker Pruitt, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 12, 2026
Assembly type
RP
Serial number
W156913
Size
1
Test gauge serial
G-9839
Gauge calibration date
Dec 9, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 053-71-01222
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

670 Quarry Rd
Owner: Cameron Marsh
Parcel 053-71-01222