Backflow assembly test: 8293 Ridgeview Way
ApprovedFiled Jan 24, 2024 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 24, 2024
- Assembly type
- RP
- Serial number
- K507876
- Size
- 3/4
- Test gauge serial
- G-4034
- Gauge calibration date
- Sep 30, 2023
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Hollins, current on the service date
- All required fields present
- Address matches parcel 053-68-01015
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.