Backflow assembly test: 8501 Pine Knoll Way
ApprovedFiled Jan 6, 2025 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 6, 2025
- Assembly type
- PVB
- Serial number
- A438246
- Size
- 1
- Test gauge serial
- G-2744
- Gauge calibration date
- Jun 27, 2024
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Kessler, current on the service date
- All required fields present
- Address matches parcel 053-19-01298
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.