Back to the backflow review queue
Backflow assembly test: 3403 Old Church Way
ApprovedFiled Aug 2, 2023 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 2, 2023
- Assembly type
- RP
- Serial number
- K623710
- Size
- 3/4
- Test gauge serial
- G-4970
- Gauge calibration date
- Nov 24, 2022
- Check valve 1
- 8.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 053-68-01030
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3403 Old Church Way
Owner: Cameron Kessler
Parcel 053-68-01030