Back to the backflow review queue

Backflow assembly test: 3126 Hickory Ln

Approved

Filed Jun 10, 2023 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 10, 2023
Assembly type
RP
Serial number
Z548906
Size
1
Test gauge serial
G-2457
Gauge calibration date
Dec 16, 2022
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 053-75-01006
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3126 Hickory Ln
Owner: Sam Kessler
Parcel 053-75-01006