Backflow assembly test: Hilltop Medical Offices

Approved

Filed Dec 1, 2024 by Rowan Benton, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 1, 2024
Assembly type
DC
Serial number
B272886
Size
4
Test gauge serial
G-7940
Gauge calibration date
Jun 17, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-46-01329
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.