Back to the backflow review queue
Backflow assembly test: 1433 Pine Knoll Dr
ApprovedFiled Jul 1, 2024 by Cameron Kessler, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 1, 2024
- Assembly type
- RP
- Serial number
- Z176183
- Size
- 3/4
- Test gauge serial
- G-9937
- Gauge calibration date
- Oct 23, 2023
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Kessler, current on the service date
- All required fields present
- Address matches parcel 053-61-01177
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1433 Pine Knoll Dr
Owner: Parker Fairley
Parcel 053-61-01177