Backflow assembly test: 8414 Mill Creek Ct

Approved

Filed Dec 26, 2025 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 26, 2025
Assembly type
DC
Serial number
B969210
Size
3/4
Test gauge serial
G-1652
Gauge calibration date
Sep 22, 2025
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-91-01001
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8414 Mill Creek Ct
Owner: Rowan Kessler
Parcel 053-91-01001