Backflow assembly test: 2085 Meadow Lark Ln

Filed Nov 18, 2026 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 18, 2026
Assembly type
RP
Serial number
Z934167
Size
3/4
Test gauge serial
G-4448
Gauge calibration date
Aug 15, 2025
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
3 psid
Relief valve opened at
4.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-62-01018
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.