Backflow assembly test: 2085 Meadow Lark Ln

Approved

Filed Dec 7, 2024 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 7, 2024
Assembly type
RP
Serial number
Z934167
Size
3/4
Test gauge serial
G-7888
Gauge calibration date
May 22, 2024
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 053-62-01018
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.