Back to the backflow review queue
Backflow assembly test: Hilltop Grill
ApprovedFiled Aug 9, 2026 by Parker Fairley, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 9, 2026
- Assembly type
- RP
- Serial number
- W437197
- Size
- 1 1/2
- Test gauge serial
- G-6102
- Gauge calibration date
- Nov 26, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 053-70-01070
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3679 Sycamore Rd
Owner: Kessler Holdings LLC
Parcel 053-70-01070