Backflow assembly test: 9227 Cedar Hollow Ln

Approved

Filed May 9, 2026 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 9, 2026
Assembly type
PVB
Serial number
A185384
Size
1
Test gauge serial
G-9159
Gauge calibration date
Aug 10, 2025
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 053-77-01345
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9227 Cedar Hollow Ln
Owner: Parker Benton
Parcel 053-77-01345