Approved

Filed Mar 2, 2024 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 2, 2024
Assembly type
RP
Serial number
W505059
Size
1 1/2
Test gauge serial
G-4282
Gauge calibration date
Dec 2, 2023
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Hollins, current on the service date
  • All required fields present
  • Address matches parcel 053-94-01003
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

759 Mill Creek Rd
Owner: Wexler Holdings LLC
Parcel 053-94-01003