Backflow assembly test: Golden Bakery

Approved

Filed Jun 12, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 12, 2026
Assembly type
RP
Serial number
B709489
Size
1 1/2
Test gauge serial
G-2901
Gauge calibration date
Mar 8, 2026
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-69-01216
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.