Backflow assembly test: Golden Bakery
ApprovedFiled May 15, 2025 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 15, 2025
- Assembly type
- RP
- Serial number
- B709489
- Size
- 1 1/2
- Test gauge serial
- G-1193
- Gauge calibration date
- Dec 18, 2024
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Benton, current on the service date
- All required fields present
- Address matches parcel 053-69-01216
- Readings in range, no flags
- Result: passing. Next due date resets when approved.