Backflow assembly test: 6884 Turkey Hill Dr

Approved

Filed Mar 18, 2026 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 18, 2026
Assembly type
RP
Serial number
K374300
Size
1
Test gauge serial
G-4238
Gauge calibration date
Dec 5, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-46-01356
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.