Back to the backflow review queue

Backflow assembly test: 2583 Sycamore Rd

Approved

Filed Jun 4, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 4, 2026
Assembly type
RP
Serial number
A258134
Size
3/4
Test gauge serial
G-5632
Gauge calibration date
Nov 1, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-69-01169
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2583 Sycamore Rd
Owner: Emerson Ellery
Parcel 053-69-01169