Back to the backflow review queue
Backflow assembly test: Two Rivers Car Wash
ApprovedFiled Jan 18, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 18, 2026
- Assembly type
- RP
- Serial number
- K116639
- Size
- 1 1/2
- Test gauge serial
- G-2044
- Gauge calibration date
- Apr 5, 2025
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Benton, current on the service date
- All required fields present
- Address matches parcel 053-36-01331
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8640 Cedar Hollow Trl
Owner: Wexler Holdings LLC
Parcel 053-36-01331