Backflow assembly test: Riverside Bakery

Approved

Filed Jan 21, 2025 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 21, 2025
Assembly type
RP
Serial number
K454586
Size
2
Test gauge serial
G-3890
Gauge calibration date
Nov 27, 2024
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-50-01348
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8607 Orchard Rd
Owner: Ramirez Holdings LLC
Parcel 053-50-01348