Back to the backflow review queue
Backflow assembly test: Station Car Wash
ApprovedFiled Jun 22, 2025 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 22, 2025
- Assembly type
- RP
- Serial number
- W661398
- Size
- 4
- Test gauge serial
- G-8216
- Gauge calibration date
- Jan 17, 2025
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Kessler, current on the service date
- All required fields present
- Address matches parcel 053-47-01203
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6329 Old Church Trl
Owner: Okafor Holdings LLC
Parcel 053-47-01203