Backflow assembly test: 4964 Sycamore Way

Approved

Filed Dec 16, 2023 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 16, 2023
Assembly type
RP
Serial number
Z301580
Size
1
Test gauge serial
G-4502
Gauge calibration date
Jun 17, 2023
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 053-84-01123
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4964 Sycamore Way
Owner: Alex Fairley
Parcel 053-84-01123