Backflow assembly test: 8867 Old Church Trl
ApprovedFiled May 7, 2026 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 7, 2026
- Assembly type
- DC
- Serial number
- B289398
- Size
- 3/4
- Test gauge serial
- G-9077
- Gauge calibration date
- Mar 26, 2026
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-35-01289
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8867 Old Church Trl
Owner: Quinn Benton
Parcel 051-35-01289