ApprovedFiled Jul 16, 2025 by Parker Nguyen, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 16, 2025
- Assembly type
- DC
- Serial number
- K132170
- Size
- 2
- Test gauge serial
- G-7221
- Gauge calibration date
- Apr 5, 2024
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-29-01113
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.