Backflow assembly test: 4790 Orchard Ln
ApprovedFiled Dec 31, 2023 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 31, 2023
- Assembly type
- RP
- Serial number
- W943066
- Size
- 3/4
- Test gauge serial
- G-7214
- Gauge calibration date
- Nov 12, 2023
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1 psid
- Relief valve opened at
- 3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ramirez, current on the service date
- All required fields present
- Address matches parcel 051-41-01263
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.