Backflow assembly test: 3522 Ridgeview Dr

Approved

Filed Oct 12, 2025 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 12, 2025
Assembly type
RP
Serial number
B995386
Size
1
Test gauge serial
G-9220
Gauge calibration date
Jun 11, 2025
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-55-01160
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.